Installing
4.9 Connecting the interfaces for the inverter control
4.9.10

Connecting the inverter to PROFIBUS

The PROFIBUS DP interface has the following functions:
● Cyclic communication
● Acyclic communication
● Diagnostic alarms
General information on PROFIBUS DP can be found in the Internet:
● PROFIBUS user organization (http://www.profibus.com/downloads/installation-guide/)
● Information about PROFIBUS DP
support/printkatalog.htm)
4.9.10.1

Connecting the PROFIBUS cable to the inverter

Procedure
To connect the inverter to a control via PROFIBUS DP, proceed as follows:
1. Integrate the inverter into the bus system (e.g. line topology) of the control using PROFIBUS
cables via socket X126.
The maximum permitted cable length to the previous station and the subsequent one is
100 m at a baud rate of 12 Mbit/s.
2. Externally supply the inverter with 24 VDC through terminals 31 and 32.
The external 24 V supply is only required if communications with the control should also
run when the line voltage is switched off.
You have now connected the inverter to the control using PROFIBUS DP.
Communication with the controller even when the supply voltage on the Power Module is
switched off
You must supply the Control Unit with 24 V DC at terminals 31 and 32 if you wish to maintain
communication with the control system when the line voltage is switched off.
In the case of brief interruptions of the 24 V power supply, the inverter may signal a fault without
communications with the control system being interrupted.
108
Overview of the interfaces (Page 81)
(http://www.automation.siemens.com/net/html_76/
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
SINAMICS G120C converter

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c dpSinamics g120c pn

Table of Contents