Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Figure 5-8
Ramp-down time after the OFF3 command
Motor data identification: Select the method which the inverter uses to measure the data of
the connected motor:
● OFF: Motor data is not measured.
STIL ROT: Recommended setting: Measure the motor data at standstill and with the motor
rotating.
The inverter switches off the motor after the motor data identification has been completed.
● STILL: Default setting: Measure the motor data at standstill.
The inverter switches off the motor after the motor data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a mechanically limited traversing
range.
● ROT: Measure the motor data while it is rotating.
The inverter switches off the motor after the motor data identification has been completed.
● ST RT OP: setting same as STIL ROT.
The motor accelerates to the currently set setpoint after the motor data identification.
● STILL OP: setting same as STILL.
The motor accelerates to the currently set setpoint after the motor data identification.
Complete quick commissioning:
● Switch over the display using an arrow key: nO → YES
● Press the OK key.
You have completed quick commissioning.
5.4.5

Expert

Select the motor standard:
● KW / 50HZ: IEC
● HP / 60HZ: NEMA
● KW / 60HZ: IEC 60 Hz
Specify the overload capability of the inverter:
● HIGH OVL: Load cycle with "High Overload"
● LOW OVL: Load cycle with "Low Overload"
128
Ramp-up and ramp-down time of the motor
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF