Siemens SINAMICS G120C USS/MB Operating Instructions Manual page 455

Sinamics g120c series low voltage converter built-in units with frame sizes aa - f
Hide thumbs Also See for SINAMICS G120C USS/MB:
Table of Contents

Advertisement

3.
4.
You have performed the acceptance test of the STO function.
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
Select STO
3.1.
Select STO while the motor is running.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2.
Check the following:
When controlled via
PROFIsafe
● The inverter signals
the following:
"STO selection via
PROFIsafe"
(r9772.20 = 1)
● If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains
at standstill.
● The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
● The inverter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
Deselect STO
4.1.
Deselect STO.
4.2.
Check the following:
● STO is not active (r9773.1 = 0).
● The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
A.6 Acceptance test for the safety function
When controlled via a fail-
safe F-DI digital input
● The inverter signals
the following:
"STO Selection via
terminal"
(r9772.17 = 1)
Appendix
When controlled via
STO_A and STO_B ter‐
minals on a PM240‑2 or
PM240P‑2 Power Mod‐
ule
● The inverter signals
the following:
"STO Selection via
terminal on Power
Module"
(r9772.25 = 1)
Status
455