You have backed up the settings of the inverter on the memory card.
Procedure with Startdrive
Proceed as follows to back up the inverter settings to a memory card:
1. Go online.
2. Select "Online & diagnostics".
3. Select "Backing up/reset".
4. Back up the settings to the EEPROM of the inverter.
5. Select the settings as shown in the diagram.
6. Start data transfer
7. Wait until Startdrive has signaled that the data backup has been completed.
You have backed up the inverter settings to a memory card.
Procedure with BOP-2
Proceed as follows to back up your settings on a memory card:
1. Remove any USB cable that is inserted in the inverter.
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
2. In the "OPTIONS" menu, select "TO CARD".
3. Set the number of your data backup. You can back up 99 different settings
on the memory card.
4. Start data transfer with OK.
5. Wait until the inverter has backed up the settings to the memory card.
Saving settings and series commissioning
7.1 Saving settings on a memory card
325