Terminal Strips - Siemens SINAMICS G120C USS/MB Operating Instructions Manual

Sinamics g120c series low voltage converter built-in units with frame sizes aa - f
Hide thumbs Also See for SINAMICS G120C USS/MB:
Table of Contents

Advertisement

Installing
4.9 Connecting the interfaces for the inverter control
4.9.3

Terminal strips

Terminal strips for FSAA ... FSC with wiring example
Figure 4-24
Wiring example of the digital inputs with the internal inverter 24 V power supply
All terminals with the reference potential "GND" are connected to each other inside the inverter.
Reference potentials "DI COM1" and "DI COM2" are electrically isolated from "GND".
→ if, as described above, you use the 24‑V power supply from terminal 9 to supply the digital
inputs, then you must connect "GND" with "DI COM1" and "DI COM2" at the terminals.
When an optional 24-V power supply is connected to terminals 31, 32, the Control Unit remains
in operation even after the Power Module has been disconnected from the line supply. The
Control Unit thus maintains fieldbus communication, for example.
→ for terminals 31, 32 only use a 24 VDC power supply with PELV (Protective Extra Low
Voltage).
→ for applications in the USA and Canada: Use a 24 VDC power supply, NEC Class 2.
→ connect the 0 V of the power supply with the protective conductor.
→ if you also wish to use the power supply at terminals 31, 32 for the digital inputs, then you
must connect "DI COM1/2" and "GND IN" with one another at the terminals.
For the analog input, you can use the internal 10-V power supply or an external voltage source.
Typical current consumption: 10 mA ... 20 mA.
84
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
SINAMICS G120C converter

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c dpSinamics g120c pn

Table of Contents