Siemens SINAMICS G120C USS/MB Operating Instructions Manual page 366

Sinamics g120c series low voltage converter built-in units with frame sizes aa - f
Hide thumbs Also See for SINAMICS G120C USS/MB:
Table of Contents

Advertisement

Alarms, faults and system messages
8.5 List of alarms and faults
Number
Cause
F30004
Inverter overtemperature
F30005
I2t inverter overload
F30011
Line phase failure
F30015
Motor cable phase failure
F30021
Ground fault
F30022
Power Module: Monitoring U
F30027
Time monitoring for DC link pre-
charging
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30052
Incorrect Power Module data
F30053
Error in FPGA data
F30059
Internal fan defective
F30074
Communications error between
Control Unit and Power Module
A30502
DC link overvoltage
F30662
CU hardware fault
F30664
CU power up aborted
F30850
Software fault in the Power Mod‐
ule
A30920
Temperature sensor fault
366
Remedy
Check whether the inverter fan is running.
Check whether the ambient temperature is in the permissible range.
Check whether the motor is overloaded.
Reduce the pulse frequency.
Check the rated currents of the motor and inverter.
Reduce the current limit p0640.
When operating with V/f characteristic: Reduce p1341.
Check the inverter's input fuses.
Check the motor cables.
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
● Check the power cable connections.
● Check the motor.
● Check the current transformer.
● Check the cables and contacts of the brake connection (a wire might be
broken).
Check or replace the inverter.
CE
Check the line voltage.
Check the line voltage setting (p0210).
● Check whether the fan is running.
● Check the fan filter elements.
● Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
● Check the motor load.
● Check the line phases
Check the internal fan and if required replace.
Replace the inverter or upgrade the inverter firmware.
Replace the inverter.
Check the internal fan and if required replace.
There is a communications fault between the Control Unit and the Power
Module. Possible cause:
● The external 24 V Control Unit power supply has dipped to ≤95% of the
rated voltage for ≤3 ms
● Check the device supply voltage (p0210).
● Check the line reactor dimensioning
Switch off the inverter and switch on again, upgrade the firmware or contact
technical support.
Switch off the inverter and switch on again, upgrade the firmware or contact
technical support.
Replace the inverter or contact technical support.
Check that the sensor is connected correctly.
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
SINAMICS G120C converter