Parameter
Parameter
p0010
p0230
p0235
p0350
p0352
Additional information on the parameters is provided in the List Manual.
6.19.2

V/f control

Overview of the U/f control
The U/f control is a closed-loop speed control with the following characteristics:
● The inverter controls the output voltage using the V/f characteristic
● The output frequency is essentially calculated from the speed setpoint and the number of
pole pairs of the motor
● The slip compensation corrects the output frequency depending on the load and thus
increases the speed accuracy
● Not using a PI controller prevents the speed control from becoming unstable
● In applications in which greater speed accuracy is required, a closed-loop control with load-
dependent voltage boost can be selected (flux current control, FCC)
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
Description
Drive commissioning parameter filter (factory setting: 1)
0: Ready
2: Power unit commissioning
Drive filter type, motor side (factory setting: 0)
0: No filter
1: Output reactor
2: dv/dt filter
3: Siemens sine-wave filter
4: Sine wave filter, third-party manufacturer
Number of motor reactors in series (factory setting: 1)
Number of reactors connected in series at the inverter output
Motor stator resistance, cold (factory setting: 0 Ω)
When selecting a list motor (p0301), p0350 is preset (default setting) and is write protec‐
ted.
Cable resistance (Factory setting: 0 Ω)
If you set p0352 after the motor data identification, then you must subtract the difference
that was changed with p0352, from the stator resistance p0350 or repeat the motor data
identification.