Number
Cause
A50001
PROFINET configuration error
A50010
PROFINET name of station inva‐
lid
A50020
PROFINET: Second control
missing
For further information, please refer to the List Manual.
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
Remedy
A PROFINET control is attempting to establish a connection with a faulty
configuration telegram. Check whether "Shared Device" is activated (p8929
= 2).
Correct the name of station (p8920) and activate (p8925 = 2).
"Shared Device" is activated (p8929 = 2). However, only the connection to a
PROFINET control is present.
Overview of the manuals (Page 459)
Alarms, faults and system messages
8.5 List of alarms and faults
367