HPE ProLiant XL270d Gen9 User Manual page 88

Accelerator tray
Table of Contents

Advertisement

For more information about product features, specifications, options, configurations, and compatibility, see the
product QuickSpecs on the Hewlett Packard Enterprise website .
To install the component:
Procedure
1.
Back up all server data.
2.
Power down the server .
3.
Disconnect all peripheral cables from the server front panel.
4.
Remove the server from the chassis.
5.
Place the server on a sturdy, level surface.
6.
Remove the access panel.
7.
Remove the side panel.
CAUTION:
To prevent improper cooling and thermal damage, do not operate the server unless all bays are
populated with either a component or a blank.
CAUTION:
The mixing of different GPU accelerator models is not supported.
CAUTION:
If three or more NVIDIA Tesla K80 GPUs or NVIDIA Tesla P40 GPUs are installed on one side of
the server, the inlet ambient temperature must be maintained at or below 30°C (86°F).
CAUTION:
If three or more NVIDIA Tesla P100 GPUs are installed on one side of the server, the inlet ambient
temperature must be maintained at or below 25°C (77°F).
8.
If there are already NVIDIA K80/M40/P40/P100 GPUs installed in the server, and additional
K80/M40/P40/P100 GPUs are now being installed, remove the GPU blank:
a. Loosen the captive screw.
b. Using both hands, gently pull the tab and the rear of the GPU blank.
c. Slide out the GPU blank from the server.
9.
If NVIDIA K80/M40/P40/P100 GPUs are not installed in the server, remove all GPUs:
88
Hardware options installation