VACON · 166
CAUTION!
The warranty is void if the Fire mode function is activated! You can use Test mode
to test the Fire mode function and the warranty stays valid.
P3.16.12 FIRE MODE RUN INDICATION CURRENT
This parameter has only effect if 'Run indication' is selected as the option for a relay output
and the Fire mode is active. The 'Run indication' relay output functionality tells quickly if
current is supplied to the motor during a fire.
The value of this parameter is the percentage counted from the motor nominal current. If
there is a fire and the current that is supplied to the motor is more than the nominal current
times the value of this parameter, the relay output closes.
For example, if the Motor nominal current is 5 A, and you set the default value 20 % for this
parameter, the relay output closes and Fire Mode activates when the output current goes to
1 A.
NOTE!
This parameter does not have an effect if the Fire mode is not active. In normal
operation, if you select 'Run indication' as the option for a relay output, the result is
the same as when 'Run' is selected for the relay output.
9.14

APPLICATION SETTINGS

P3.17.4 FUNCT BUTTON CONFIGURATION
This parameter tells which selections show when you push the Funct button.
Local / Remote
Control Page
Change Direction (only visible in keypad control)
9
PARAMETER DESCRIPTIONS