Vacon 100 hvac Applications Manual page 16

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

VACON · 16
Table 2: Quick Setup parameter group
Index
Parameter
Motor Nominal Volt-
P1.1
age
Motor Nominal Fre-
P1.2
quency
Motor Nominal
P1.3
Speed
Motor Nominal Cur-
P1.4
rent
P1.5
Motor Cos Phi
P1.6
Motor nominal power
P1.7
Motor Current Limit
P1.8
Minimum Frequency
P1.9
Maximum Frequency
I/O Control Refer-
P1.10
ence A Selection
P1.11
Preset frequency 1
P1.12
Preset frequency 2
1
Min
Max
Unit
Varies
Varies
V
8.0
320.0
Hz
24
19200
rpm
Varies
Varies
A
0.30
1.00
Varies
Varies
kW
Varies
Varies
A
0.00
P1.9
Hz
P1.8
320.00
Hz
1
8
P3.3.1
300.00
Hz
P3.3.1
300.00
Hz
QUICK STARTUP GUIDE
Default
ID
Description
Find this value U
Varies
110
the nameplate of the
motor. See P3.1.1.1.
Find this value f
50
111
the nameplate of the
motor. See P3.1.1.2.
Find this value n
Varies
112
the nameplate of the
motor.
Find this value I
Varies
113
the nameplate of the
motor.
Find this value on the
Varies
120
nameplate of the
motor.
Find this value n
Varies
116
the nameplate of the
motor.
The maximum motor
Varies
107
current from the AC
drive.
The minimum fre-
Varies
101
quency reference that
is acceptable.
The maximum fre-
50.00
102
quency reference that
is acceptable.
The selection of the
frequency reference
6
117
source when the con-
trol place is I/O A. See
P3.3.3 for selections.
Select with the digital
input: Preset frequency
10.00
105
selection 0 (P3.5.1.15)
(Default = Digital Input
4)
Select with the digital
input: Preset frequency
15.00
106
selection 1 (P3.5.1.16)
(Default = Digital Input
5)
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
on
n
on
n
on
n
on
n
on
n

Advertisement

Table of Contents
loading