PARAMETERS MENU
Table 33: Setpoint settings
Index
Parameter
P3.12.2.8
Sleep Delay 1
P3.12.2.9
Wake-up Level 1
Setpoint 1 Wake-up
P3.12.2.10
Mode
P3.12.2.11
Setpoint 1 boost
Setpoint source 2
P3.12.2.12
selection
P3.12.2.13
Setpoint 2 minimum
P3.12.2.14
Setpoint 2 maximum
Sleep Frequency
P3.12.2.15
limit 2
P3.12.2.16
Sleep Delay 2
P3.12.2.17
Wake-up Level 2
Setpoint 2 Wake-up
P3.12.2.18
mode
P3.12.2.19
Setpoint 2 boost
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0
3000
s
0.01
100
x
0
1
-2.0
2.0
x
0
16
-200.00
200.00
%
-200.00
200.00
%
0.00
320.00
Hz
0
3000
s
Varies
0
1
-2.0
2.0
x
Default
ID
Description
The minimum quantity of
time during which the
0
1017
frequency has to stay
below the sleep level
before the drive stops.
If the PID controller is in
sleep mode, it starts the
drive and regulates
when it goes below this
0
1018
level. Absolute level or
relative to the setpoint
based on WakeUpMode
parameter.
The selection for the
operation of P3.12.2.9.
0
15539
0 = Absolute level
1 = Relative setpoint
It is possible to boost the
1.0
1071
setpoint with a digital
input.
See P3.12.2.4.
2
431
The minimum value at
0.00
1073
the analogue signal min-
imum.
The maximum value at
100.00
1074
the analogue signal
maximum.
See P3.12.2.7.
0.00
1075
0
1076
See P3.12.2.8.
0.0000
1077
See P3.12.2.8.
The selection for the
operation of P3.12.2.17.
0
15540
0 = Absolute level
1 = Relative setpoint
1.0
1078
See P3.12.2.11.
VACON · 93