PARAMETER DESCRIPTIONS
VACON · 161
M1
M2
M3
M4
M5
Starting order of motors
Fig. 41: The interlock logic 1
The sequence of the motors is 1, 2, 3, 4, 5.
If you remove the interlock of Motor 3, that is, you set the value of P3.5.1.36 is set to OPEN,
the sequence changes to 1, 2, 4, 5.
ID428 =FALSE
M1
M2
M3
M4
M5
Starting order of motors
Fig. 42: The interlock logic 2
If you add Motor 3 again (you set the value of P3.5.1.36 to CLOSED), the system puts Motor 3
last in the sequence: 1, 2, 4, 5, 3. The system does not stop, but continues to operate.