PARAMETERS MENU
Table 39: Setpoints
Index
Parameter
P3.13.2.1
Keypad Setpoint 1
P3.13.2.2
Keypad Setpoint 2
P3.13.2.3
Setpoint Ramp Time
Setpoint Source 1
P3.13.2.4
Selection
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0.00
100.00
Varies
0.00
100.00
Varies
0.00
300.00
s
0
16
Default
ID
Description
0.00
1640
0.00
1641
0.00
1642
0 = Not Used
1 = Keypad Setpoint 1
2 = Keypad Setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 =ProcessDataIn1
10 =ProcessDataIn2
11 =ProcessDataIn3
12 =ProcessDataIn4
13 =ProcessDataIn5
14 =ProcessDataIn6
15 =ProcessDataIn7
16 =ProcessDataIn8
The AIs and the Proc-
essDataIn show as per-
centages (0.00-100.00%)
and use the setpoint
1
1643
minimum and maximum
for scaling.
NOTE!
The ProcessDataIn sig-
nals use 2 decimals.
If temperature inputs
are selected, you must
set the values of
parameters P3.14.1.8
Process Unit Max and
P3.14.1.9 Process Unit
Min to agree with the
scale of the tempera-
ture measurement
board:
ProcessUnitMin = -50
°C
ProcessUnitMax = 200
°C
VACON · 99