Vacon 100 hvac Applications Manual page 92

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

VACON · 92
Table 33: Setpoint settings
Index
Parameter
P3.12.2.1
Keypad setpoint 1
P3.12.2.2
Keypad setpoint 2
P3.12.2.3
Setpoint ramp time
Setpoint source 1
P3.12.2.4
selection
P3.12.2.5
Setpoint 1 minimum
P3.12.2.6
Setpoint 1 maximum
P3.12.2.7
Sleep Frequency
limit 1
5
Min
Max
Unit
Varies
Varies
Varies
Varies
Varies
Varies
0.00
300.0
s
0
16
-200.00
200.00
%
-200.00
200.00
%
0.00
320.00
Hz
PARAMETERS MENU
Default
ID
Description
0
167
0
168
Gives the rising and fall-
ing ramp times for the
setpoint changes. That
0.00
1068
is, the time to change
from the minimum to
the maximum.
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
1
332
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
AI's and ProcessDataIn
are handled as percen-
tages (0.00- 100.00%)
and scaled according to
the setpoint minimum
and maximum.
ProcessDataIn signals
use two decimals.
The minimum value at
0.00
1069
the analogue signal min-
imum.
The maximum value at
100.00
1070
the analogue signal
maximum.
The drive goes to sleep
mode when the output
frequency stays below
0.00
1016
this limit for a longer
time than set by Sleep
Delay.