PARAMETER DESCRIPTIONS
5. CS2 activates again and causes the
motor to accelerate (REV) to the set
frequency.
6. CS2 becomes inactive and the frequency
that is fed to the motor goes to 0.
7. CS1 activates and the motor accelerates
(FWD) to the set frequency.
8. The Run enable signal is set to OPEN,
which causes the frequency to go to 0.
Configure the Run enable signal with
parameter P3.5.1.10.
9. The Run enable signal is set to CLOSED,
which does not have an effect, because a
rising edge is necessary for the start,
even if CS1 is active.
Selection
Selection name
number
CS1 = Start
3
CS2 = Reverse
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
10. The STOP button on the keypad is
pushed and the frequency that is fed to
the motor goes to 0. (This signal only
works if the value of P3.2.3 Keypad Stop
Button is Yes.)
11. CS1 is opened and closed again, which
causes the motor to start.
12. CS1 becomes inactive and the frequency
that is fed to the motor goes to 0.
Description
VACON · 129
9