VACON · 58
Table 10: Motor control settings
Index
Parameter
P3.1.2.18
Energy Optimization
P3.1.2.19
Flying Start Options
P3.1.2.20
I/f Start
P3.1.2.21
I/f Start Frequency
P3.1.2.22
I/f Start Current
5
Min
Max
Unit
0
1
0
1
0
1
5.0
25
Hz
0
100
%
PARAMETERS MENU
Default
ID
Description
The drive finds the
minimum motor cur-
rent to save energy and
to lower the motor
noise. You can use this
function for example in
0
666
fan and pump applica-
tions.
0 = Disabled
1 = Enabled
0 = Search the shaft
direction from both
directions
1 = Search the shaft
1590
frequency only from
the same direction as
the frequency refer-
ence
0
534
0 = Disabled
1 = Enabled
The output frequency
0.2 *
limit below which the
535
P3.1.1.2
set I/f start current is
fed to motor.
The current that is fed
to the motor when the
80
536
I/f Start function is
activated.