Vacon 100 hvac Applications Manual page 60

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

VACON · 60
Table 11: Start/stop setup menu
Index
Parameter
P3.2.6
I/O A Start/Stop
Logic
I/O B Start/Stop
P3.2.7
Logic
P3.2.8
Fieldbus Start Logic
5
Min
Max
Unit
0
4
0
4
0
1
PARAMETERS MENU
Default
ID
Description
Logic = 0
Ctrl sgn 1 = Forward
Ctrl sgn 2 = Backward
Logic = 1
Ctrl sgn 1 = Forward
(edge)
Ctrl sgn 2 = Inverted
Stop
Logic = 2
0
300
Ctrl sgn 1 = Forward
(edge)
Ctrl sgn 2 = Bckwrd
(edge)
Logic = 3
Ctrl sgn 1 = Start
Ctrl sgn 2 = Reverse
Logic = 4
Ctrl sgn 1 = Start
(edge)
Ctrl sgn 2 = Reverse
See above.
0
363
0 = A rising edge is
0
889
necessary
1 = State