VACON · 56
Table 10: Motor control settings
Index
Parameter
P3.1.2.1
Switching Frequency
P3.1.2.2
Motor Switch
Zero Frequency Volt-
P3.1.2.4
age
Motor preheat func-
P3.1.2.5
tion
5
Min
Max
Unit
1.5
Varies
kHz
0
1
0.00
40.00
%
0
3
PARAMETERS MENU
Default
ID
Description
If you increase the
switching frequency,
the capacity of the AC
drive reduces. To
reduce capacitive cur-
rents in the motor
Varies
601
cable, when the cable
is long, we recommend
that you use a low
switching frequency.
To reduce the motor
noise, use a high
switching frequency.
When you enable this
function, the drive does
not trip when the
motor switch is closed
and opened, for exam-
0
653
ple in a flying start.
0 = Disabled
1 = Enabled
This parameter gives
the zero frequency
voltage of the U/f
Varies
606
curve. The default
value is different for
different unit sizes.
0 = Not used
1 = Always in stop state
2 = Controlled by DI
3 = Temp limit (heat-
sink)
0
1225
You can activate the
virtual digital input
with Real Time Clock