PARAMETERS MENU
Table 15: Analogue input settings
Index
Parameter
P3.5.2.1
AI1 Signal Selection
P3.5.2.2
AI1 Filter Time
P3.5.2.3
AI1 Signal Range
P3.5.2.4
AI1 Custom. Min
P3.5.2.5
AI1 Custom. Max
P3.5.2.6
AI1 Signal Inversion
P3.5.2.7
AI2 Signal Selection
P3.5.2.8
AI2 Filter Time
P3.5.2.9
AI2 Signal Range
P3.5.2.10
AI2 Custom. Min
P3.5.2.11
AI2 Custom. Max
P3.5.2.12
AI2 Signal Inversion
P3.5.2.13
AI3 Signal Selection
P3.5.2.14
AI3 Filter Time
P3.5.2.15
AI3 Signal Range
P3.5.2.16
AI3 Custom. Min
P3.5.2.17
AI3 Custom. Max
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0.0
300.0
s
0
1
-160.00
160.00
%
-160.00
160.00
%
0
1
0.0
300.0
s
0
1
-160.00
160.00
%
-160.00
160.00
%
0
1
0.0
300.0
s
0
1
-160.00
160.00
%
-160.00
160.00
%
Default
ID
Description
Connect the AI1 signal
to the analogue input
AnIN
377
of your choice with this
SlotA.1
parameter. Program-
mable.
The filter time for the
analogue input. A value
higher than 0 activates
the low pass filtering
1.0
378
function for this signal.
The filtering time is the
time it takes to reach
63 % of a step change
in the signal.
0 = 0–10V / 0–20mA
0
379
1 = 2–10V / 4–20mA
The custom range min-
0.00
380
imum setting, 20% = 4–
20 mA/2–10 V
The custom range
100.00
381
maximum setting.
0 = Normal
0
387
1 = Signal inverted
AnIN
See P3.5.2.1
388
SlotA.2
1.0
389
See P3.5.2.2
1
390
See P3.5.2.3
0.00
391
See P3.5.2.4
100.00
392
See P3.5.2.5
0
398
See P3.5.2.6
AnIN
See P3.5.2.1
141
Slot0.1
1.0
142
See P3.5.2.2
0
143
See P3.5.2.3
0.00
144
See P3.5.2.4
100.00
145
See P3.5.2.5
VACON · 71