Vacon 100 hvac Applications Manual page 63

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

PARAMETERS MENU
Table 12: Control reference settings
Index
Parameter
P3.3.12
Preset Frequency 1
P3.3.13
Preset Frequency 2
P3.3.14
Preset Frequency 3
P3.3.15
Preset Frequency 4
P3.3.16
Preset Frequency 5
P3.3.17
Preset Frequency 6
P3.3.18
Preset Frequency 7
Preset alarm fre-
P3.3.19
quency
Motor Potentiometer
P3.3.20
Ramp Time
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
P3.3.1
P3.3.1
Hz
P3.3.1
P3.3.1
Hz
P3.3.1
P3.3.1
Hz
P3.3.1
P3.3.1
Hz
P3.3.1
P3.3.1
Hz
P3.3.1
P3.3.1
Hz
P3.3.1
P3.3.1
Hz
P3.3.1
P3.3.2
Hz
0.1
500.0
Hz/s
Default
ID
Description
Make the selection
with digital input Pre-
10.00
105
set frequency selection
0 (P3.5.1.15).
Make the selection
with digital input Pre-
15.00
106
set frequency selection
1 (P3.5.1.16).
Make the selection
with digital inputs Pre-
20.00
126
set frequency selection
0 & 1.
Make the selection
with digital input Pre-
25.00
127
set frequency selection
2 (P3.5.1.17).
Make the selection
with digital inputs Pre-
30.00
128
set frequency selection
0 & 2.
Make the selection
with digital inputs Pre-
40.00
129
set frequency selection
1 & 2.
Make the selection
with digital inputs Pre-
50.00
130
set frequency selection
0 & 1 & 2.
This frequency is used
when the fault
response (in Group 3.9:
Protections) is Alarm
25.00
183
+preset frequency. Use
this frequency only
when the fault that
triggered this alarm
frequency is active.
The rate of change in
the motor potentiome-
10.0
331
ter reference when it is
increased or
decreased.
VACON · 63
5

Advertisement

Table of Contents
loading

Table of Contents