Vacon 100 hvac Applications Manual page 178

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

VACON · 178
Table 61: Fault codes
Fault
Fault ID
code
52
1052
1352
53
1053
54
1354
1454
1654
1754
65
1065
66
1066
69
1310
1311
1312
101
1101
105
1105
10
Fault name
Possible cause
Keypad communica-
The connection between the
tion fault
control panel and the drive
is defective.
Fieldbus communica-
The data connection
tion fault
between the fieldbus master
and the fieldbus board is
defective.
Slot A fault
A defective option board or
slot
Slot B fault
Slot D fault
Slot E fault
PC communication
The data connection
fault
between the PC and the
drive is defective
Thermistor fault
The motor temperature
increased.
Fieldbus mapping
The ID number that is used
error
to map the values to Field-
bus Process Data Out is not
valid.
It is not possible to convert 1
or more values for Fieldbus
Process Data Out.
There is an overflow when
the values for Fieldbus
Process Data Out (16-bit)
are mapped and converted.
Process supervision
The PID controller: the feed-
fault (PID1)
back value is not in the
supervision limits and the
delay, if you set the delay.
Process supervision
The PID controller: the feed-
fault (PID2)
back value is not in the
supervision limits and the
delay, if you set the delay.
FAULT TRACING
How to correct the fault
Do a check of the control panel
connection and the control panel
cable.
Do a check of the installation and
fieldbus master.
Do a check of the board and the
slot.
Do a check of the motor cooling
and the load. Do a check of the
thermistor connection. If the ther-
mistor input is not used, you have
to short-circuit it.
Do a check of the parameters in
the Fieldbus Data Mapping menu.
The type of the value is undefined.
Do a check of the parameters in
the Fieldbus Data Mapping menu.