VACON · 70
Table 14: Digital input settings
Index
Parameter
P3.5.1.39
Fire Mode Activation OPEN
P3.5.1.40
Fire Mode Activation CLOSE
P3.5.1.41
Fire Mode Reverse
P3.5.1.42
Keypad CTRL
P3.5.1.43
Reset kWh Trip Counter
Fire mode preset frequency
P3.5.1.44
selection 0
Fire mode preset frequency
P3.5.1.45
selection 1
P3.5.1.46
Param. Set 1/2 Sel.
5
Default
ID
DigIN Slot0.2
1596
DigIN Slot0.1
1619
DigIN Slot0.1
1618
DigIn Slot0.1
410
DigIn Slot0.1
1053
DigIn Slot0.1
15531
DigIn Slot0.1
15532
DigIN Slot0.1
496
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
PARAMETERS MENU
Description
Activates the Fire mode if it is ena-
bled with a correct password.
OPEN = Active
CLOSED = Inactive
Activates the Fire mode if it is ena-
bled with a correct password.
OPEN = Inactive
CLOSED = Active
Gives a command of reverse rotation
direction during Fire mode. This
function has no effect in normal
operation.
Forces control place to keypad.
Resets the kWh Trip Counter
Before you can activate the selection,
set the Fire Mode frequency source
to Fire Mode frequency.
Before you can activate the selection,
set the Fire Mode frequency source
to Fire Mode frequency.
Selection for the parameter set (1 or
2).
OPEN = Parameter Set 1
CLOSED = Parameter Set 2