Vacon 100 hvac Applications Manual page 22

Hide thumbs Also See for 100 hvac:
Table of Contents

Advertisement

VACON · 22
Set a value for parameter P3.17.3 Fire Mode Fre-
2
quency
Activate the signal when the contact opens or when
it closes
3
Set a value for parameters P3.17.4 Fire Mode Acti-
4
vation on OPEN / P3.17.5 Fire Mode Activation on
CLOSE
Set a value for parameter P3.17.6 Fire Mode
Reverse
5
Set a value for P3.17.1 Fire Mode Password
6
2
8.00 Hz...P3.3.1.2 (MaxFreqRef)
0 = Open contact
1 = Closed contact
Make a selection of a digital input to activate
Fire mode. See also Chapter 9.13 Fire mode.
Make a selection of a digital input to activate
the reverse direction in Fire mode.
DigIn Slot0.1 = FORWARD
DigIn Slot0.2 = REVERSE
Set a password to enable the Fire mode func-
tion.
1234 = Enable test mode
1001 = Enable Fire mode
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
WIZARDS

Advertisement

Table of Contents
loading

Table of Contents