Verifying The Ieee C37.118/1344 Tcp Communication - ABB REG670 Commissioning Manual

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UUS A
Establishing connection and verifying the IEEE C37.118/1344 communication
11.5.1
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
communication
explains how to set the PMU Connection Tester parameters in order to
establish an IEEE C37.118 connection with the PMU.

Verifying the IEEE C37.118/1344 TCP communication

After setting both PMU configuration and the TCP client configuration (As explained
in sections
Setting the PMU station communication (PMU
station communication (PMU configuration)
communication) and making sure that the Ethernet communication is set up, click
Connect on the PMU Connection Tester tool.
IEC140000138 V1 EN-US
Figure 30:
Verifying the TCP communication using PMU Connection Tester
Now it should be possible to see the streaming synchrophasor data. In the Graph
tab, observe the Frequency, data Reporting Rate, Phasor names, and Phase angles
of the reported synchrophasors. Observe the real-time frame details of the Data
Frame in the bottom of the window.
GUID-289E2E92-431E-45FE-B586-A723588B98A1 v1
Report),
Setting the PMU
and
Setting the TCP/UDP client
IEC140000138-1-en.vsd