Measuring The Trip Value For The Zero-Sequence Function - ABB REG670 Commissioning Manual

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UUS A
13.9.2.3
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
2
×
=
+
×
3
V
V
a V
2
A
B
EQUATION1818-ANSI V1 EN-US
Where:
V V
V
and
A
B
C
EQUATION1820-ANSI V1 EN-US
p ×
2
j
= ×
= -
a
1
e
0, 5
3
IECEQUATION00022 V2 EN-US
4.
Compare the result with the set value of the negative-sequence operating voltage
(consider that the set value 3V2PU is in percentage of the base voltage VBase).
5.
Repeat steps
1
and 2. Then slowly increase the measured current in one phase
until the BLKV signal disappears.
6.
Record the measured current and calculate the corresponding negative-sequence
current according to the equation (observe that the currents in the equation are
phasors):
×
=
+
2
×
+ ×
3
I
I
a
I
2
A
B
ANSIEQUATION00021 V1 EN-US
Where:
,
I
I and I
A
B
C
ANSIEQUATION00020 V1 EN-US
p ×
2
j
= ×
= -
a
1
e
0, 5
3
IECEQUATION00022 V2 EN-US
7.
Compare the result with the set value of the negative-sequence operating current.
Consider that the set value 3I2< is in percentage of the base current IBase.

Measuring the trip value for the zero-sequence function

Measure the trip value for the zero-sequence function, if included in the IED.
Testing functionality by secondary injection
+ ×
a V
C
are the measured phase voltages
3
+
.
j
2
a I
C
are the measured phase currents
3
+
.
j
2
Section 13
(Equation 107)
(Equation 108)
M1405-72 v11
243

Advertisement

Table of Contents
loading

Table of Contents