Repair Instruction - ABB REG670 Commissioning Manual

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UUS A
16.3
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
Headline
GOOSE is configured on a disabled port
LDCM not running the application image
LDCM version is not accepted
OEM not running the application image
SFP unplugged from the slot
SFP replaced with other type
Non ABB vendor SFP detected

Repair instruction

Never disconnect the secondary connection of a current transformer
circuit without short-circuiting the transformer's secondary winding.
Operating a current transformer with the secondary winding open will
cause a massive potential build up that may damage the transformer
and may cause injuries to humans.
Never connect or disconnect a wire and/or a connector to or from a IED
during normal service. Hazardous voltages and currents are present that
Troubleshooting
Explanation
At least one of the access points configured for
GOOSE is disabled. The port can be disabled
either through changing the access point operation
to off or by unchecking the GOOSE protocol from
the access point in the Ethernet configuration in
PCM600 or LHMI.
Please enable GOOSE on access points:
AP_FRONT, AP_1
<slot number> is running the factory image instead
of the application image. The factory image is older
and does not contain the latest updates and fixes.
Please reboot the IED. If the problem persists
update the LDCM firmware or replace the board.
<device name> firmware version <version string>
is not accepted. The minimum accepted version is
<version string>.
Please update the LDCM firmware or replace the
board.
OEM in slot <slot number> is running the factory
image instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists,
update the OEM firmware or replace the board.
SFP has been unplugged from the slot
Please check the connection.
Corresponding hardware(s) is set to fail.
Configured and the detected SFP(s) are different.
Corresponding hardware(s) is set to fail.
Please restart IED and consider Reconfigure HW
modules to get updated hardware list.
Non ABB vendor SFP detected.
Corresponding hardware(s) is set to fail. Please
use ABB approved SFP's.
Section 16
IP8767-1 v1
M11764-2 v2
303