Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
IEC10000141 V2 EN-US
Figure 48:
Trajectory of the impedance Z(R, X) for the injected current with two
components: a 50 Hz component and a 49.5 Hz current component
The test of the out-of-step protection function requires the injection of the analog
quantities for a quite long time. The rating of the analogue channels is considered in
order to avoid any hardware damage. The test current is lower than the continuous
permissive overload current I
module.
If the rated secondary current I
current test I
is
ts
I
I
4
I
4
A
= ×
=
ts
ovrl
rs
EQUATION14041 V1 EN-US
If the CT of the generator has ratio 9000/1 A, then in primary values
I
9000
rp
I
I
I
4
=
×
= ×
t
ovrl p
,
ovrl
I
rs
EQUATION14042 V1 EN-US
Reference is made to the numerical values of the example, explained in the "Setting
guidelines" of the Application Manual. A test current equal to 2.5 time the base current
of the generator is chosen; this choice is related to the selected test voltage that is
applied while testing the point SE and RE.
I
2 5
.
I
2 5 8367 20918
.
=
×
=
×
t
Base
EQUATION14043 V1 EN-US
Testing functionality by secondary injection
I = I(50 Hz) + I(49.5 Hz)
of the protection current channels of the transformer
ovrl
of the analog channel is 1 A, then the maximum
rs
36000
A
=
1
A
=
Section 13
(Equation 1)
(Equation 2)
(Equation 3)
161