Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
Testing functionality by secondary injection

Testing disturbance report

Introduction

The following sub-functions are included in the disturbance report function:
Disturbance recorder
Event list
Event recorder
Trip value recorder
Indications
If the disturbance report is enabled, then its sub-functions are also set up and so it is
not possible to only disable these sub-functions. The disturbance report function is
disabled (parameter Operation = Disabled) in PCM600 or the local HMI under Main
menu/Settings/IED Settings/Monitoring/Disturbance report/DRPRDRE:1.

Disturbance report settings

When the IED is in test mode, the disturbance report can be made active or inactive. If
the disturbance recorder is turned on during test mode, recordings will be made. When
test mode is switched off all recordings made during the test session are cleared.
Setting OpModeTest for the control of the disturbance recorder during test mode are
located on the local HMI under Main menu/Settings/IED Settings/Monitoring/
Disturbance report/DRPRDRE:1.

Disturbance recorder (DR)

A Manual Trig can be started at any time. This results in a recording of the actual
values from all recorded channels.
The Manual Trig can be started in two ways:
1.
From the local HMI under Main menu/Disturbance records.
1.1. Enter on the row at the bottom of the HMI called Manual trig.
Testing functionality by secondary injection