Establishing connection and verifying the LON communication
The HV Control 670 software module and 670 series Object Type files
are used with both 650 and 670 series IEDs.
Use the LON Network Tool (LNT) to set the LON communication. This is a software
tool applied as one node on the LON bus. To communicate via LON, the IEDs need to
know
The node addresses of the other connected IEDs.
The network variable selectors to be used.
This is organized by LNT.
The node address is transferred to LNT via the local HMI by setting the parameter
ServicePinMsg = Yes. The node address is sent to LNT via the LON bus, or LNT can
scan the network for new nodes.
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This can
be changed by LNT.
The LON communication setting parameters are set via the local HMI. Refer to the
Technical manual for more detailed specifications.
If LON communication from the IED stops because of illegal communication
parameter settings (outside the setting range) or due to other kind of disturbance, it is
possible to reset the IED's LON port.
LON communication setting parameters (Table 14) and LON node information
parameters (Table 15) can only be set via the LON Network Tool (LNT).
Some of these parameters can be viewed on the local HMI under Main menu/
Configuration/Communication/Station communication/Port configuration/SLM
optical LON port/LONGEN:1.
Table 14:
LON communication setting parameters
Parameter
Range
DomainID
0
SubnNetAddr*
0 - 255
Step: 1
NodeAddr*
0 - 127
Step: 1
*Can be viewed on the local HMI
Default
Unit
Parameter description
0
-
Domain identification number
0
-
Subnet address
0
-
Node address
Section 9
M11888-3 v5
M11643-1 v4
103