Measuring The Trip And Time Limit For Set Values - ABB REG670 Commissioning Manual

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
Testing functionality by secondary injection
13.5.6.1
194
IED test set
NI
V_A
V_B
V_C
V_N
ANSI09000021 V1 EN-US
Figure 54:
Principle connection of the test set
Values of the logical signals belonging to the sensitive directional residual overcurrent
and power protection are available on the local HMI under Main menu/Test/Function
status/Current protection/SensDirResOvCurr(67N,IN>)/SDEPSDE(67N,IN>):x

Measuring the trip and time limit for set values

Operation mode 3I
0
Procedure
1.
Set the polarizing voltage to 1.2 · VNRelPU and set the phase angle between
voltage and current to the set characteristic angle (RCADir). Note that the the
current lagging the voltage.
Take setting RCAComp into consideration if not equal to 0.
2.
Inject current until the function picks up, and make sure that the trip current of
the set directional element is equal to the INcosPhiPU setting.
The I Dir (3I
· cosφ) function activates the PICKUP and PUNDIN output.
0
3.
Assume that φ´ is the phase angle between injected voltage (3V
(3I
) i.e. φ´ = RCADir-φ. Change φ´ to for example 45 degrees. Increase the
0
injected current until the function trips.
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
NI
V1
V2
V3
V_N
TRIP
ANSI09000021-1-en.vsd
· cosφ
1MRK 502 073-UUS A
IED
) and current
0
Commissioning manual
SEMOD175060-12 v2
SEMOD175060-34 v9