Section 13
Testing functionality by secondary injection
252
No operation
ANSI05000551 V1 EN-US
Figure 64:
Test of phase difference
3.
Change the phase angle between +dφ and -dφ and verify that the two outputs are
activated for phase differences between these values but not for phase differences
outside, see figure 64.
Testing the frequency difference
The frequency difference test should verify that operation is achieved when the
FreqDiffA and FreqDiffM frequency difference is lower than the set value for manual
and auto synchronizing check, FreqDiffA and FreqDiffM respectively and that
operation is blocked when the frequency difference is greater.
Test with frequency difference = 0 mHz
Test with a frequency difference outside the set limits for manual and auto
synchronizing check respectively.
1.
Apply voltages V-Line equal to 100% GblBaseSelLine and V-Bus equal to 100%
GblBaseSelBus, with a frequency difference equal to 0 mHz and a phase
difference lower than the set value.
2.
Check that the AUTOSYOK and MANSYOK outputs are activated.
3.
Apply voltage to the V-Line equal to 100% GblBaseSelLine with a frequency
equal to 50 Hz and voltage V-Bus equal to 100% GblBaseSelBus, with a
frequency outside the set limit.
4.
Check that the two outputs are not activated. The test can be repeated with
different frequency values to verify that the function trips for values lower than
the set ones. If a modern test set is used, the frequency can be changed
continuously.
Testing the reference voltage
1.
Use the same basic test connection as in figure 62.
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
V-Bus
+dj
V-Line operation
-dj
V-Bus
en05000551_ansi.vsd
1MRK 502 073-UUS A
M2377-232 v9
M2377-249 v5
Commissioning manual