ABB REG670 Commissioning Manual page 305

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UUS A
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
HMI Signal Name:
Status
BIMnn
READY / FAIL
BOMn
READY / FAIL
IOMn
READY / FAIL
MIMn
READY / FAIL
RTC
READY / FAIL
Time Sync
READY / FAIL
Application
READY / FAIL
RTE
READY / FAIL
IEC61850
READY / FAIL
LMD
READY / FAIL
LDCMxxx
READY / FAIL
OEM
READY / FAIL
Also the internal signals, such as INT--FAIL and INT--WARNING can be connected to
binary output contacts for signalling to a control room.
In the IED Status - Information, the present information from the self-supervision
function can be viewed. Indications of failure or warnings for each hardware module
are provided, as well as information about the external time synchronization and the
internal clock. All according to table 26. Loss of time synchronization can be
considered as a warning only. The IED has full functionality without time
synchronization.
Description
BIM error. Binary input module Error
status. Signal activation will reset the
IED
BOM error. Binary output module Error
status.
IOM-error. Input/Output Module Error
status.
mA input module MIM1 failed. Signal
activation will reset the IED
This signal will be active when there is a
hardware error with the real time clock.
This signal will be active when the
source of the time synchronization is
lost, or when the time system has to
make a time reset.
This signal will be active if one or more
of the application threads are not in the
state that Runtime Engine expects. The
states can be CREATED, INITIALIZED,
RUNNING, etc.
This signal will be active if the Runtime
Engine failed to do some actions with the
application threads. The actions can be
loading of settings or parameters for
components, changing of setting groups,
loading or unloading of application
threads.
This signal will be active if the IEC 61850
stack did not succeed in some actions
like reading IEC 61850 configuration,
startup etc.
LON network interface, MIP/DPS, is in
an unrecoverable error state.
Line Differential Communication Error
status
Optical Ethernet Module error status
Section 16
Troubleshooting
299