Section 13
Testing functionality by secondary injection
13.4.5.3
170
Test of the boundary between zone 1 and zone 2, which is defined by
ReachZ1
the parameter
The trajectory of the impedance traverses the lens characteristic in zone
2
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related
to phase L1):
V
VT s
,
V
1 1
.
V
=
×
×
ts
t RZ
,
1
V
VT p
,
EQUATION14065 V1 EN-US
ForwardX
V
arctan
=
ts
ForwardR
EQUATION14058 V1 EN-US
frequency of V
= 50 Hz
ts
I
CTs
I
I
10459
=
×
=
50
s
50
I
CTp
EQUATION14059 V1 EN-US
∠I
= 0º
50s
frequency of I
= 50 Hz
50s
I
CTs
It
I
10459
=
×
=
tf
fs
I
CTp
EQUATION14062 V1 EN-US
∠I
= 0º
tfs
frequency of I
= 50 Hz
tfs
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are
according to the injected quantities and that ROTORANG is close to 3.14 rad. For
this particular injection the service values are:
VOLTAGE = 1.58 kV
CURRENT = 20918 A
R = 1.08%
X = 7.85%
ROTORANG = -3.04 rad
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
0 1
.
1 1 1435
.
11 44
.
V
=
×
×
=
13 8
.
59 33
.
arctan
82. . 14°
 =
 =
8 19
.
1
= .
1 162
A
×
9000
1
1 162
.
A
×
=
9000
1MRK 502 073-UUS A
GUID-BE180E07-7D4B-4842-81FB-244DE8897430 v1
GUID-17F6AC8D-1F57-4245-A61D-776D469DD153 v1
GUID-3D42E43D-873E-4271-9AAF-3B2789FF3B17 v1
(Equation 37)
(Equation 38)
(Equation 39)
(Equation 40)
Commissioning manual