ABB REG670 Commissioning Manual page 119

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UUS A
Establishing connection and verifying the IEEE C37.118/1344 communication
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
2.1. Set Host IP to the PMU IP address configured for the port in use. Here the
LANAB:1 IPAddress (192.168.1.10) is set.
2.2. Set Port to the IED's TCP port set in the PMU under parameter
C37.118TCPport (4712 is default). Alternatively, in order to make an
IEEE1344 communication, the 1344TCPport parameter setting can be used
(4713 is default).
2.3. Set the Protocol as IEEE C37.118.2-2011.
2.4. Set the Device ID Code in PMU Connection Tester per PMU Data Stream
ID Number (IDCODE). The PMU Data Stream ID Number is a user
assigned ID number (1-65534) for each data stream sent out from the PMU
and it is defined under parameter PMUdataStreamIDCODE. (Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Report/PMUREPORT:1)
2.5. Make sure that the Configure Alternate Command Channel is set as Not
Defined. The Configure Alternate Command Channel is used to configure a
TCP channel to control the UDP data communication and transfer the
header, configuration and command frames.
2.6. Continue to the section
communication.
3.
Set the Connection Parameters on PMU Connection Tester for UDP
communication according to the PMU configuration.
IEC140000136 V1 EN-US
3.1. Set the Local Port to UDP destination port defined in the PMU under the
parameter UDPDestPort1 (Default value: 8910).
3.2. Click the Configure Alternate Command Channel to configure the TCP
channel. A new window will pop up. A TCP channel needs to be configured
in order to control the UDP data communicatiuon and transfer the header,
configuration and command frames.
Verifying the IEEE C37.118/1344 TCP
Section 11
IEC140000136-1-en.vsd
113