ABB REG670 Commissioning Manual page 55

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UUS A
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
Setting up IP addresses
Communication between the IED and PCM600 is enabled from the LHMI. The IP
address and the corresponding communication subnetwork mask must be set via the
Ethernet configuration tool (ECT) for each available Ethernet interface in the IED.
Each Ethernet interface has a default factory IP address when the IED is delivered. The
IP adress and the subnetwork mask might have to be reset when an additional Ethernet
interface is installed or an interface is replaced.
DHCP is available for the front port, and a device connected to it can thereby
obtain an automatically assigned IP address via the local HMI path Main menu/
Configuration/Communication/Ethernet configuration/Front port/DHCP or,
Alternatively the default IP address for the IED front port is 10.1.150.3 and the
corresponding subnetwork mask is 255.255.255.0, which can be set via the local
HMI path Main menu/Configuration/Communication/Ethernet configuration/
AP_FRONT.
Setting up the PC or workstation for point-to-point access to IEDs front
port
An ethernet cable (max 2 m length) with RJ-45 connectors is needed to connect two
physical Ethernet interfaces together without a hub, router, bridge or switch in
between.
1.
Select Search programs and files in the Start menu in Windows.
Section 4
Starting up
49