ABB REG670 Commissioning Manual page 169

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UUS A
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual
and the voltages that are related to them:
2
V
Z
I
R
=
×
=
t FwdZ
,
FwdZ
t
FwdR
EQUATION14052 V1 EN-US
2
V
Z
I
R
=
×
=
+
t RvsZ
,
RvsZ
t
RvsR
EQUATION14053 V1 EN-US
The previous calculations are in primary values. They are transferred to secondary
values to perform injections by a test set. Primary values are transferred to secondary
values by taking into account the CT ratio and the VT ratio (respectively 9000/1 A and
13.8/0.1 kV in the example).
The magnitude of the secondary voltages, that are related to the points RE and SE of
the R-X plane, needs to be checked.
RE (R
, X
):
FwdR
FwdX
V
VT s
,
V
V
11931
=
×
=
t FwdZs
t FwdZ
,
,
V
VT p
,
EQUATION14054 V1 EN-US
SE (R
, X
):
RvsR
RvsX
V
VT s
,
V
V
5899
=
×
=
t RvsZs
,
t RvsZ
,
V
VT p
,
EQUATION14055 V1 EN-US
The tests, which are described in this section, may require voltages that have
magnitude equal to 110% of the previous values. The continuous permissive overload
voltage of the protection voltage channels of the TRM module is 420 V; so the
previous voltages may be applied to the analog channels of the IED continuously.
Limitations may be related to the available test set; the current I
using a factor 2.5 (instead of the maximum value 4) in order to reduce the magnitude
of the test voltage for the points RE and SE.
Test sets usually do not have a feature to simulate a real network during a power swing
and apply the related analog quantities at the terminal of the generator. The scope of
the present test is not a simulation of a real network. Voltages and currents are supplied
in order to measure an impedance that changes in the time and traverses the plane R-X
and, in particular, the area inside the lens characteristic. The test may be performed by
applying:
Symmetric three-phase voltage at 50 Hz. The magnitude depends on the point of
the characteristic that needs to be verified. The following three main points of the
line segment SE-RE need to be checked:
Testing functionality by secondary injection
2
2
X
I
0 078
.
0 565
.
+
×
=
+
FwdX
t
2
2
X
I
0 003
.
0 282
.
×
=
+
RvsX
t
0 1
.
V
86 45
.
×
=
13 8
.
0 1
.
42 75
.
V
×
=
13 8
.
Section 13
2
20918 0 570 0 20918 11931
.
×
=
×
=
2
20918 0 282 2 20918 5899
.
×
=
×
=
was calculated by
t
V
(Equation 12)
V
(Equation 13)
(Equation 14)
(Equation 15)
163