Boolean output signals for the injected current with two components: a
50 Hz current component and a 49.5 Hz current component

Loss of excitation LEXPDIS (40)

Prepare the IED for verification of settings outlined in Section
verify
settings".

Verifying the settings

The test is done by means of injection of three phase current and three phase voltage
from a modern test device. This test device shall be able to give voltage and current
corresponding to the set apparent impedance.
1.
Feed the IED with current and voltage corresponding to the apparent impedance:
Test #1, as shown in figure 50. Read the analog outputs for R and X and check
Testing functionality by secondary injection
COMMON TRIP COMMAND (trip)
TRIPZ1 (tripZone1)
TRIPZ2 (tripZone2)
START (start)
GENMODE (generatorMode)
MOTMODE (motorMode)
1.5
2
2.5
3
time in seconds
Section 13
3.5
4
4.5
5
IEC10000142-1-en.vsd
SEMOD158873-3 v3
"Preparing the IED to