Verifying The Settings - ABB REG670 Commissioning Manual

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
Testing functionality by secondary injection
13.4.5.1
160
pole-slip is usually allowed before the generator-transformer unit is disconnected. A
parameter setting is available to take into account the circuit breaker opening time. If
there are several out-of-step relays in the power system, then the one which finds the
center of oscillation in its zone 1 should operate first.
Two current channels I3P1 and I3P2 are available in OOSPPAM function to allow the
direct connection of two groups of three-phase currents; that may be needed for very
powerful generators, with stator windings split into two groups per phase, when each
group is equipped with current transformers. The protection function performs a simple
summation of the currents of the two channels I3P1 and I3P2.

Verifying the settings

The test of the out-of-step protection function is made to verify that the trip is issued if
the following events happen.
the impedance, seen by the function, enters the lens characteristic from one side
and leaves it from the opposite side
the trip is issued according to the settings TripAngle and tBreaker
The tripping zone needs to be detected and confirmed. The test may be performed by
taking into account the following key points that are shown in Figure 48:
the point RE (RE = Receiving End)
the intersection between the line segment SE-RE and the X-line, which is defined
through the setting ReachZ1
the point SE (SE = Sending End)
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
1MRK 502 073-UUS A
GUID-708C4033-3111-481F-9868-FF207C18C9F9 v1
Commissioning manual