ABB REG670 Commissioning Manual page 154

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
Testing functionality by secondary injection
148
Table 19:
Test points for phase-to-phase loops A-B (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPPZx x tan (LdAngle)
R
0.85 x RFPPZx
6
X
RLdFwd x tan (LdAngle)
R
RLdFwd
7
X
0
R
RLdFw
8
X
–0.2143 x RFPPZx/2
R
0.8 x RFPPZx/2
9
X
–0.4 x RLdFwd x tan(ArgDir=20°)
R
0.4 x RLdFwd
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPPZx
Table
19
is used in conjunction with figure 42.
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
set
set
set
set
+ RFPPZx/2
set
set
+ RFPPZx/2
set
set
set
set
set
set
set
1MRK 502 073-UUS A
Comments
LdAngle = angle for the maximal load
transfer
Exact: 0.8 x RFPPZx/2 (ArgDir=20°)
Exact –0.5 x R1
x tan(ArgNegRes=30°)
set
Exact –0.5 x R1
x tan(ArgNegRes=30°)
set
Commissioning manual