Advertisement

Section 13
Testing functionality by secondary injection
13.16
13.16.1
13.16.1.1
284
ANSI07000188 V1 EN-US
Figure 66:
Test of RTC with I/O

Basic IED functions

Parameter setting group handling SETGRPS

Prepare the IED for verification of settings as outlined in section
this chapter.

Verifying the settings

1.
Check the configuration of binary inputs that control the selection of the active
setting group.
2.
Browse to the ActiveGroup menu to achieve information about the active setting
group.
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
1MRK 502 073-UUS A
SEMOD52026-1 v1
M11369-2 v4
"Preparing for test"
in
M11369-4 v4
Commissioning manual