Section 4
Starting up
4.11
4.11.1
56
are still isolated and the IED is in test mode. Before removing the test handle, check
the measured values in the IED.
Not until the test handle is completely removed, the trip and alarm circuits are restored
for operation.
Verify that the contact sockets have been crimped correctly and that
they are fully inserted by tugging on the wires. Never do this with
current circuits in service.
Current circuit
1.
Verify that the contacts are of current circuit type.
2.
Verify that the short circuit jumpers are located in the correct slots.
Voltage circuit
1.
Verify that the contacts are of voltage circuit type.
2.
Check that no short circuit jumpers are located in the slots dedicated for voltage.
Trip and alarm circuits
1.
Check that the correct types of contacts are used.

Checking the binary input/output circuits

Do not insert anything else to the female connector but the
corresponding male connector. Inserting anything else (such as a
measurement probe) may damage the female connector and prevent a
proper electrical contact between the printed circuit board and the
external wiring connected to the screw terminal block.

Binary input circuits

Preferably, disconnect the binary input connector from the binary input cards. Check
all connected signals so that both input level and polarity are in accordance with the
IED specifications.
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
1MRK 502 073-UUS A
M11722-2 v4
M11722-4 v3
Commissioning manual