ABB REG670 Commissioning Manual page 220

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
Testing functionality by secondary injection
214
Third part of the characteristic (VHighLimit/100*VBase ≤ Restrain voltage):
Picup Curr
_
IBase
×
×
100
ANSIEQUATION2434 V1 EN-US
Example (rated secondary current = 5A):
CT ratio
VT ratio
Pickup_Curr
VDepFact
VHighLimit
IBase
VBase
A test for each section of the characteristic of the function VRPVOC may be
performed; that may be achieved by applying the following voltages:
First section of the characteristic:
If VDepMode = Slope, the minimum measured phase-to-phase voltage is lower
than 0,25*VBase; if VDepMode = Step, the minimum measured phase-to-phase
voltage is lower than VHighLimit/100*VBase:
VA: Ampl = 10 / √3; Angle = 0°
VB: Ampl = 10 / √3; Angle = 240°
VC: Ampl = 100 / √3; Angle = 120°
Second section of the characteristic only:
If VDepMode = Slope, the minimum measured phase-to-phase voltage is between
0,25*VBase and VHighLimit/100*VBase:
VA: Ampl = 50 / √3; Angle = 0°
VB: Ampl = 50 / √3; Angle = 240°
VC: Ampl = 100 / √3; Angle = 120°
Last section of the characteristic:
If VDepMode = either Slope or Step, the minimum measured phase-to-phase
voltage is higher than VHighLimit/100*VBase:
VA: Ampl = 105/ √3; Angle = 0°
VB: Ampl = 105/ √3; Angle = 240°
VC: Ampl = 105 / √3; Angle = 120°
4.
Inject the voltages that are related to the first part of the characteristic, and then
slowly increase the phase current IA from 0.0 A up to the value the function trips.
The PICKUP and STOC signals must be activated when the amplitude of the
phase current IA is slightly above 0.25 A on the secondary side. The
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
CT
sec
CTprim
10 000/5A
10 kV/100 V
100%
25%
100%
10 000 A
10 kV
1MRK 502 073-UUS A
(Equation 91)
Commissioning manual