ABB REG670 Commissioning Manual page 124

Relion 670 series, generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 11
Establishing connection and verifying the IEEE C37.118/1344 communication
118
IEC140000141 V1 EN-US
Figure 33:
All the IEEE C37.118 message types
It is also possible to capture the IEEE C37.118 synchrophasor data in an Excel file.
This is done by navigating to File/Capture/Start Stream Debug Capture... The
tool will ask to Set Stream Debug Capture File Name and path to save the
capture file.
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
1MRK 502 073-UUS A
IEC140000141-1-en.vsd
Commissioning manual