Segregated Phase Comparison System - Ametek UPLC-II System Manual

Universal power-line carrier
Table of Contents

Advertisement

3.5.5 Segregated Phase Comparison
System
The Segregated Phase Comparison system has
been developed to improve pilot relay protection,
particularly for the long EHV series capacitor-
compensated transmission lines. Long EHV series
capacitor-compensated lines are a source of sig-
nificant transients during the fault period. Under
these circumstances, sequence current networks
designed to operate at normal system frequency
may present a problem. The experience with these
Phase Comparison systems has, however, been
remarkably good. Directional Comparison sys-
tems, on the other hand, are subject to mis-opera-
tion on series capacitor-compensated lines, partic-
ularly if the capacitor gaps do not short the capac-
itors on faults. Segregated phase comparison sys-
tems, which are current-only, are independent of
the following phenomena:
• Power system frequency and wave form
• Effects of impedance unbalance between
the power system phase circuits.
• Maximum load/minimum fault current
margin.
The segregated phase comparison system can be
divided into two types: a two-subsystem scheme
and a three-subsystem scheme. In the two-subsys-
tem scheme, one subsystem operates from delta
current (I a -I b ) for all multi-phase faults, and a
ground (3I 0 ) current subsystem operates for all
ground faults. The three-subsystem scheme has a
subsystem for each phase (I a , I b , and I c ). Each
subsystem consists of one channel (UPLC-II™)
and one Phase Comparison relay.
Both segregated Phase Comparison systems
incorporate "offset keying", enabling them to trip
for internal high-resistance ground faults and
internal faults with outfeed at one terminal. No
other system can clear these types of faults with-
out extra logic or channels. On a 500 kV line with
a 2,000:5 current transformer ratio, for example,
January 2016
Chapter 3. applications
the three-subsystem scheme will operate for
ground-fault resistances up to about 100 Ω pri-
mary impedance. Under the same conditions, the
two-subsystem scheme will operate up to about
200 Ω primary fault resistance.
The two-subsystem package is suitable for all
applications except single-pole tripping, where the
three-subsystem package must be applied. The
basic operation of the scheme is illustrated in
Figure 3–12. Each current is fed through a nonin-
ductive resistor, supplying a voltage output to the
squaring amplifier (SA) that is exactly proportion-
al to the primary currents. The output of these
amplifiers is used to key the individual channels
and, through the local delay timers (LDT), to pro-
vide the local square waves for comparison. The
timers are adjustable between 2 and 20ms to com-
pensate for the delay time of the channel. This dig-
ital delay circuit translates the pulse train inde-
pendently of the pulse width ratio, in contrast to
the ac phase angle shift used in the other systems.
The ac phase shift delay uses frequency-depen-
dent components, which are accurate only at sys-
tem frequency and can "ring" during transient
conditions.
The square wave comparison is made independ-
ently for each current in the separate subsystems.
Separate channels are required for each of the sub-
systems. One of the comparison circuits is shown
in simplified form in Figure 3–13. In this dual
comparison circuit, AND-P is used for the positive
half-cycles and AND-N for the negative half-
cycles. As shown in Figure 3–13, the received
positive square wave corresponds to a "1" input to
AND-P, and the received negative square wave to
a "0" input, negated to "1", into AND-N. Except
for this variation, operation is as shown by the
square wave blocks in the lower half of Figure 3–
11.
3
Page 3–21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents