Ametek UPLC-II System Manual page 107

Universal power-line carrier
Table of Contents

Advertisement

In addition to the XML file, you may save a report file that is more readable. A sample is provided here:
Software Revision:
4.01
Unit IP:
10.14.3.52
MAC Address:
00:07:5E:00:20:1C
Catalog Number:
US1NEM9AFSX
Date/Time:
Fri Sep 19 14:30:30 2014
System ID (Major): Substation X
System ID (Minor): Line Y
General Settings
Channel Type:
Function :
Rear Ethernet Mode:
Transmit Frequency:
Receive Frequency:
TX Shift-Bandwidth:
RX Shift-Bandwidth:
RF coax connection:
RF Impedance:
Transmit Power Low:
Transmit Power High:
RX Sensitivity:
Fade Alarm:
Fade Margin:
Reflected Power Alarm: 15 %
Transmitter:
Receiver:
Current margin:
Current receive level: 9 dB
Current transmit power: 30 dBm
Current reflected power: 0.0%
Session Time Out:
Logic Settings
CB Trip Test:
Line Relay Settings
Pre-Trip Delay:
Trip Hold:
Guard Hold:
Unblock Timer:
Unblock Delay:
Guard Before Trip: Required
Direct Transfer Trip Settings
Pre-Trip Delay:
Trip Hold:
Guard Hold:
Guard Before Trip: Required
Input Output Settings
Inputs
1. Hold:
Selection:
Active State: Application of Voltage
Voltage:
2. Hold:
Selection:
Active State: Application of Voltage
Voltage:
3. Hold:
Selection:
Active State: Application of Voltage
Voltage:
4. Hold:
Selection:
Active State: Application of Voltage
Voltage:
5. Hold:
Selection:
Active State: Application of Voltage
Voltage:
January 2016
FSK
3-Frequency
Redundant
250.00 kHz
252.00 kHz
600 ± 250
600 ± 250
4 Wire
50
Ohms
1.0 W
10.0 W
118.1 mV
10 dB
15 dB
Enabled
Enabled
15.0 dB
30 Min.
Enabled
4 ms
0 ms
0 ms
150 ms
10 ms
30 ms
0 ms
0 ms
0.0 ms
LR Key
125
0.0 ms
DTT Key
125
0.0 ms
Power Off
125
0.0 ms
Trip Test
125
0.0 ms
SOE Event 1
125
Chapter 5. installation/Commissioning Procedure
Trip Duty Outputs
1. Selection:
LR Guard NC Contact
2. Selection:
LR Trip NC Contact
3. Selection:
DTT Guard NC Contact
4. Selection:
DTT Trip NC Contact
Power Supply Alarms Contacts
Main Power Supply
Redundant Power Supply: Not Installed
Low Level Outputs
1. Selection:
De-energized State:
Action:
Max Load:
2. Selection:
De-energized State:
Action:
Max Load:
3. Selection:
De-energized State:
Action:
Max Load:
4. Selection:
De-energized State:
Action:
Max Load:
5. Selection:
De-energized State:
Action:
Max Load:
6. Selection:
De-energized State:
Action:
Max Load:
7. Selection:
De-energized State:
Action:
Max Load:
8.
Selection:
De-energized State:
Action:
9.
Selection:
De-energized State:
Action:
10. Selection:
De-energized State:
Action:
Trip Test Settings
Auto Test:
Trip Test Type:
Trip Test Type:
Trip Test Hours:
Trip Test Hours:
Trip Test Hours:
Trip Test Hours:
Trip Test Period:
Options
Configuration:
Power Supply:
Redn. Power Supply: None
Outputs: Standard Outputs w/ Trip Duty
Logic:
Ethernet Ports (Rear): Redundant/Daisy
45(10/100 BaseT)
Protocols:
Front Port: Ethernet / RS-232
Testing: ON-OFF CB Test / FSK Trip Test
Power Amp Features: Improved Power Amp w/
Freq Selectivity for Refl Power
Normally Closed
LR Guard
NO
Normal
1.0A
LR Trip
NO
Normal
1.0A
DTT Guard
NO
Normal
1.0A
DTT Trip
NO
Normal
1.0A
Fade Alarm
NO
Normal
1.0A
Good Channel
NO
Normal
1.0A
TX Shift Low
NO
Normal
1.0A
Reflected Power
NO
Normal
Main RF Output
NO
Normal
General Alarm
NC
Normal
On
CB Trip
Periodic
6:00
12:00
18:00
0:00
72
Single Transceiver
110/125/250 Vdc
Standard
Chain 2 RJ-
DNP 3.0
Page 5–15