Table 5–13. (ON/OFF Mode) Input/Output Descriptions
Input Name
Carrier Start
Carrier Stop
Low Level Key
SOE Event 1/2/3
Output Name
General Alarm
Reflected Power
Main RF Output
Redundant RF Output
Fade Alarm
1
Blocking Output
2
Carrier Received
2
CB (Checkback) Outputs
Fade alarm is actually a RX level mon tor instead of an alarm in the ON/OFF mode.
1
It should activate when no carrier is transmitted and deactivate when carrier is started.
These 2 outputs are the same, even though they have different names.
2
January 2016
Chapter 5. installation/Commissioning Procedure
TX or
Action When Input Applied
RX
TX
TX carrier keyed on to high level setting (10W) default)
TX
TX carrier keyed off
TX
TX carrier keyed on to low level setting (1W default)
Both
Causes Event 1/2/3 to be recorded in SOE log
TX or
RX
Both
Any major hardware failure occurs
TX
TX % reflected power above threshold setting
TX
TX level above 0.3W on Main Power Amp
TX
TX level above 0.3W on Redundant Power Amp
RX
RX level below alarm threshold setting since last RX calibration
RX
Carrier received and blocking command issued
RX
Carrier received and blocking command issued
Both
"See Chapter 6, table 6-2."
Active State
5
Page 5–25