Operating Instructions
Z-tron IV
Point Level Control
+1 215-674-1234
+1 215-674-2731
www.drexelbrook.com
Level Measurement
Installation and
TM
Leader in

Advertisement

Table of Contents
loading

Summary of Contents for Ametek Z-tron IV

  • Page 1 Leader in Level Measurement Installation and Operating Instructions Z-tron IV Point Level Control Telephone: +1 215-674-1234 Fax: +1 215-674-2731 E-mail: drexelbrook.service@ametek.com Website: www.drexelbrook.com...
  • Page 2 AMETEK Drexelbrook makes no warranty of any kind with regard to the material contained in this manual, including, but not limited to, implied warranties or fitness for a particular purpose. Drexelbrook shall not be liable for errors contained herein or for incidental or consequential damages in connection with the performance or use of material.
  • Page 3 EDO# 5-19-110 Z-tronIV-LM Issue#5 Z-tron IV Point Level Control 205 Keith Valley Road, Horsham, PA 19044 Telephone: +1 215-674-1234 Fax: +1 215-674-2731 An ISO 9001 Certified Company E-mail: drexelbrook.info@ametek.com Website: www.drexelbrook.com...
  • Page 4 Table of Contents...
  • Page 5: Table Of Contents

    Contents Section 1: Introduction ............................1 System Description ..........................1 Technology ..............................1 Spare Parts ..............................1 Model Number............................2 Section 2: Installation ............................3 Unpacking ..............................3 Mounting the Level Control ........................3 Integral Mounting Dimensions ......................5 Remote Mounting Dimensions ......................6 3A Mounting Dimensions ........................7 Power Wiring .............................8 Relay Wiring ...............................11 Wiring the Sensing Element (Remote) .....................12 Wiring the Sensing Element (Integral) .....................13...
  • Page 6 Section 1...
  • Page 7: Introduction

    The label on top of the electronic unit identifies the model number of the Z-tron IV level control. System Description Cote-Shield™ action is designed into all Z-tron IV level controls and enables the instrument to ignore the effect of buildup or material coating on the sensing element.
  • Page 8: Model Number

    Z-tron IV Point Level Control Model Number Technology Z4 Z-tron IV RF Admittance Level Measurement System Input Power 24 VDC 115 VAC, Field Selectable 230 VAC, Field Selectable Electronics Integral (No Cable) Remote w/ 25 Ft Gp Cable Remote w/ 5 Ft Hi Temp Cable...
  • Page 9: Installation

    Extended sensing element lengths and special mountings can be provided to fit specific applications. • The Z-tron IV Level Control is designed for industrial applications, but it should be mounted in a location as free as possible from vibration, corrosive atmospheres, or any possibility of mechanical damage.
  • Page 10 WRONG CORRECT Conduit Breather Drain WRONG CORRECT Conduit Breather Drain WRONG CORRECT Figure 2-1 Z-tron IV Level Control Mounting Recommendations CONDULET Packing Hold here when Gland WRONG tightening CORRECT Assembly Condulet Do Not Disturb! Hold here to install or remove Sensing...
  • Page 11: Integral Mounting Dimensions

    Installation Integral Mounting Dimensions Figure 2-3-1 Mounting Dimensions...
  • Page 12: Remote Mounting Dimensions

    Z-tron IV Point Level Control Remote Mounting Dimensions Figure 2-3-2 Mounting Dimensions...
  • Page 13: 3A Mounting Dimensions

    Installation 3A Probe Mounting Dimensions Insertion Length Limited to 12" Insertion Length Limited to 36" For Longer Lengths Contact Factory Figure 2-3-3 3A Mounting Dimensions...
  • Page 14: Power Wiring

    AMETEK Drexelbrook representative or call 1-215-674-1234. Refer to Figures 2-4-1 and 2-4-2 for the appropriate power wiring and use the following procedure to wire the Z-tron IV level control: 1. Ensure that all power to the wiring is off.
  • Page 15 Installation Power Wiring (continued) Input Voltage Selection 115 / 230 VAC Only Figure 2-4-1 Power Wiring...
  • Page 16 Z-tron IV Point Level Control Power Wiring (continued) WARNING HIGH VOLTAGE HIGH JUMPER POSITION ELECTRICAL SHOCK HAZARD DISCONNECT POWER DISCON BEFORE CHANGING BEFOR JUMPER SELECTION JUMPER INPUT VOLTAGE INPU JUMPER SELECTION JUMPER WARNING WARNING HIGH VOLTAGE HIGH VOLTAGE JUMPER POSITION...
  • Page 17: Relay Wiring

    Installation Relay Wiring Refer to Figure 2-5 for the relay contact wiring. The Z-tron IV relay has double-pole, double-throw (DPDT) dry contacts. The relay serves as a switch and does not provide the power to operate an annunciator or other equipment. All relay connections are made to the terminal strip on the electronic unit.
  • Page 18: Wiring The Sensing Element (Remote)

    Z-tron IV Point Level Control Wiring the Sensing Element (Remote) If the Ztron electronic unit is mounted remotely from the sensing element, the cable connections from the sensing element to the electronic unit are made to the individual terminals on the side opposite the terminal strips.
  • Page 19: Wiring The Sensing Element (Integral)

    Installation Wiring the Sensing Element (Integral) NOTE It is important that the sensing element cable is Mechanically separated from the power wiring. Figure 2-7 Wiring the Integral Sensing Element...
  • Page 20: Operation

    (Up= High Level Fail Safe Down= Low Level Fail Safe) Time Delay Selector Switch (Up= Forward Acting Down= Reverse Acting) Time Delay Adjustment (Clockwise Increases Delay) Red Alarm LED Setpoint Adjustment (Clockwise Increases Level) Green Power LED Figure 3-1 Z-tron IV Operating Controls and LED...
  • Page 21: Time Delay Control

    Operation Time Delay Control The time delay adjustment is located on top of the instrument, as shown in Figure 3-1. It is used to help stop a repeated relay output due to agitation or waves in the vessel. CAUTION: THIS adjustment is a 270º (¾ turn) potentiometer. Do not turn it beyond its mechanical stops or damage to unit may occur.
  • Page 22: Failsafe

    Z-tron IV Point Level Control Failsafe Failsafe describes the level condition which causes the output relay to de-energize, and determines the condition of the relay upon loss of power or upon the failure of most components. • The failsafe mode may be selected in the field by changing the position of the right slide switch located on the top of the instrument.
  • Page 23 Section 4...
  • Page 24: Calibration

    Turn setpoint adjustment counterclockwise until red LED turns on. Set failsafe as required. All Other Sensing Elements All Z-tron IV controls are factory set to switch in conductive materials [setpoint adjustment is set to full clockwise (CW) position]. No calibration adjustment is necessary.
  • Page 25: Calibration In Insulating Material [Horizontal Mount]

    Calibration Calibration in Insulating Material [Horizontal Mount] The following procedure is for high level fail-safe. If the unit is set for low level fail-safe LED operation will be opposite: 1) Quick Calibration (Either Veritical or Horzontal): a) Be sure the material level is well below the sensing element.
  • Page 26: Calibration In Insulating Material [Vertical Mount]

    Z-tron IV Point Level Control Calibration in Insulating Material [Vertical Mount] The following procedure is for high level fail-safe. If the unit is set for low level fail-safe LED operation will be opposite: 1) Be sure the material level is well below the sensing element.
  • Page 27 Section 5...
  • Page 28: Troubleshooting

    Point Level Control Section 5: Troubleshooting Introduction The Z-tron IV Level Control is a solid-state device with no moving parts other than its relays, and requires no maintenance or adjustments. The units are designed to give years of unattended service.
  • Page 29: Testing Sensing Element

    Troubleshooting Testing Sensing Element With level below the sensing element: 1. Disconnect remote cable, if applicable. 2. Use an analog ohmmeter¹ that is set to the R x 1K ohm scale. Measure the resistances between each pair of sensing element connections. See Figure 5-1. Record values in Table.
  • Page 30 Z-tron IV Point Level Control Testing Sensing Element (continued) ANALOG ANALOG OHMMETER OHMMETER CENTER OUTER CONDUCTOR CONDUCTOR GROUNDED GROUNDED Red Lug HOUSING HOUSING PACKING PACKING GLAND GLAND DO NOT DISTURB DO NOT DISTURB PROBE MEASUREMENT SHIELD MEASUREMENT Sensing Element in Vessel...
  • Page 31: Testing Relay Circuits

    Troubleshooting The relay circuits consist of a double-pole double-throw relay brought out to a terminal strip. Figure 5-2 shows the relay when the unit is in an alarm condition Using an ohmmeter, perform the following steps to check out the relay circuits: 1.
  • Page 32: Testing Remote Cable

    Z-tron IV Point Level Control Testing Remote Cable 1. Disconnect remote cable from electronic unit and sensing element. 2. Using an ohmmeter measure the resistances as shown in Figure 5.4 A. Check for shorts. i. Connect ohmmeter to cable center wire and ground wire.
  • Page 33: Possible Problems And Causes

    Troubleshooting Factory Assistance Problem Possible Cause Solution 1. Instrument indicates a. Severe coating build on a. Need longer Cote-Shield. alarm at all times. sensing element (HLFS). Consult factory. b. Sensing element not b. Need longer insertion “seeing” material (LLFS) length. due to fill angle.
  • Page 34: Field Service

    Z-tron IV Point Level Control AMETEK Drexelbrook can answer any questions about The Z-tron IV series instrument. Call Customer Service at +1 215 674-1234. If you require assistance and attempts to locate the problem have failed: Contact your local Drexelbrook representative, Telephone the Service department: •...
  • Page 35: 5.10 Equipment Return

    • Please include a purchase order even if the repair is under warranty. If repair is covered under warranty, you will not be charged. Ship equipment freight prepaid to: AMETEK-DREXELBROOK. 205 KEITH VALLEY ROAD HORSHAM, PA 19044-1499 COD shipments will not be accepted.
  • Page 36: Specifications

    Z-tron IV Point Level Control Section 6: Specifications Power Requirements: AC Units - Field Selectable: 95-145 VAC, 50/60 Hz, 2 Watt 215-265 VAC, 50/60 Hz, 2 Watt DC Units: 24 VDC Unit: 19-29 VDC input, 2 Watt Sensitivity: 0.3pF or less...
  • Page 37 Specifications Section 6: Specifications (Continued) Housing: The standard housing meets the following classifications: Nema 1 General-Purpose Nema 2 Drip-Tight Nema 3 Weather-Resistant Nema 4 Waterproof Nema 5 Dust-Tight Nema 12 Industrial Use If hazardous area approval is required, use the Drexelbrook PXL The Point™...
  • Page 38: Appendix A: Shortening Or Lengthening The Sensing Element

    Appendix Appendix A: Shortening or Lengthening the Sensing Element The Need Sometimes your application calls for probe lengths other CAUTION: than the standard 18-inch or longer insertion lengths The insulation length of supplied. Shortening the sensing element is quite simple either Flush Sensing and can be done in the field.
  • Page 39 AMETEK, Inc. TERMS AND CONDITIONS OF SALE THE FOLLOWING TERMS/CONDITIONS, TOGETHER WITH ANY OTHER TERMS/CONDITIONS SPECIFICALLY AGREED TO IN WRITING BY SELLER, SHALL APPLY TO ALL ORDERS (“Order(s)”) FROM, AND SALES OF PRODUCTS (“Products”) OR SERVICES (“Services”) TO BUYER. ANY ACCEPTANCE OF ANY ORDER OF BUYER IS CONDITIONED UPON THESE TERMS/CONDITIONS. ANY ADDITIONAL OR DIFFERENT TERMS/CONDITIONS PROPOSED BY BUYER IN ANY DOCUMENT ARE OBJECTED TO AND SHALL NOT BE BINDING UPON SELLER.
  • Page 40 WHETHER ORAL, WRITTEN, EXPRESS, IMPLIED OR STATUTORY. Seller’s prior written consent. Upon completion of Order, Buyer shall promptly return all Data to Seller together with all copies or reprints thereof NO IMPLIED OR STATUTORY WARRANTIES OF then in Buyer's possession or control, and Buyer shall thereafter make no MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE future use, either directly or indirectly, of any Data or any information SHALL APPLY.