ONLINE MODULE CHANGE
7.1

Online Module Change Conditions

The CPU, MELSECNET/H remote I/O module, A/D converter module, GX Developer and
base unit given below are needed to perform an online module change.
(1) CPU
The Process CPU or Redundant CPU are required.
For precautions on multiple CPU system configuration, refer to the QCPU User's
Manual (Multiple CPU System).
For precautions on redundant system configuration, refer to the QnPRHCPU User's
Manual (Redundant System).
(2) MELSECNET/H remote I/O module
The module of function version D or later is necessary.
(3) A/D converter module
The module of function version C or later is necessary.
(4) GX Developer
GX Developer of Version 7.10L or later is necessary.
GX Developer of Version 8.18U or later is required to perform an online
module change on the remote I/O station.
(5) Base unit
1) When the slim type main base unit (Q3 SB) is used, an online module
change cannot be performed.
2) When the power supply module unnecessary type extension base unit
(Q5 B) is used, online module change cannot be performed for the
modules on all the base units connected.