When industrial shipment setting is used and initial setting was
made with sequence program
(1) Conversion disable
(a) Set the A/D conversion enable/disable setting (Un\G0) for all channel conversion
(2) Dismounting of module
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the

7.3.2 When industrial shipment setting is used and initial setting was made with sequence program

disable and turn operating condition setting request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the A/D conversion completion
flag (Un\G10), turn off Operation Condition Setting Request (Y9).
(The window shows the setting example of the Q68AD-G.)
"Online module change" mode, double-click the module to be changed online to
display the "Online module change" window.
7.3 Online Module Change Procedure
1
2
3
4
5
6
7
8
7
- 10